Electrical thermal imaging uses an infrared camera to find hot spots in switchboards, connections and equipment before they cause a fault, a fire or downtime. Phase Safe provides thermal imaging for commercial and industrial clients across New Zealand, from bases in Wellington and Auckland, and our licensed electricians then fix what the scan finds, from remaking connections to rebalancing loads and replacing failing parts.
What is electrical thermography?
Electrical thermography is the use of a thermal imaging camera to measure the surface temperature of electrical equipment while it is working. Parts with a problem, such as a loose connection or an overloaded cable, run hotter than the parts around them, and the camera shows that difference as an image. The images are then interpreted and reported, so you can see what needs attention and how urgent it is.
"Infrared camera" and "thermal camera" usually describe the same tool: both detect infrared radiation, which every object gives off more of as it heats up. The value is less in the camera than in the interpretation: knowing what normal looks like for each type of equipment, and telling a real fault from a reflection.
What does a thermal scan find?
A thermal scan picks up problems that make electrical parts run hot: loose, corroded or poorly made connections, overloaded circuits and cables, phase imbalance where one phase carries more load than the others, and breakers, fuses or contactors that are starting to fail. None of these is visible with the cover on, and many give no warning until something trips, melts or burns.
| Finding | What it usually points to | Typical fix |
|---|---|---|
| Single hot terminal or lug | Loose or corroded connection | Remake or replace the connection |
| Whole circuit running warm | Overloaded cable or breaker | Redistribute load or add a circuit |
| One phase hotter than the others | Phase imbalance | Rebalance loads across phases |
| Hot breaker, fuse or contactor | Component wearing out | Replace the component |
What does our thermal imaging service include?
Our thermal imaging service covers the whole job: we plan the visit with you, arrange access to your boards and equipment, scan them under normal load and report what we find with images. Our licensed electricians then quote for and carry out the repairs. You deal with one contact for both the scan and the follow-up work, instead of managing two separate contractors.
We offer thermal imaging because it fits naturally with the rest of our work. A scan without anyone to act on it is only a list of problems, and repairs without a scan rely on guesswork. A scan also pairs well with a switchboard survey, which records the condition, capacity and labelling of each board.
Which switchboards and equipment should be scanned?
Start with the main switchboard and distribution boards, because that is where connections and protective devices are concentrated. Industrial sites often add motor control panels, machinery isolators and busbars, and larger sites add switchgear and cable terminations. A scan only shows what the camera can see, so the equipment has to be running under normal load with covers safely removed.
If a scan finds a board with repeated hot spots, ageing components or no spare capacity, repairs may not be enough. Our page on switchboard upgrades covers when a board is better replaced.
How often should switchboards be thermally scanned?
How often to scan is usually set by your insurer, your maintenance plan and the risk on site. As one example, Vero's risk guide for businesses recommends thermographic checks at least once a year, carried out with the equipment under load. Check what your own insurer expects, and consider extra scans after major changes, before busy seasons, or when a board has had faults.
A yearly scan fits well into a programme of planned and predictive maintenance, alongside other checks, so the follow-up repairs can be scheduled with the rest of the work.
What happens after the thermal scan?
The report sets out what the scan found and what needs doing. We go through it with you, fix urgent items first, and plan the rest around your operations. After repairs, a follow-up scan can confirm the fault is gone. Keep every report: comparing scans year on year shows trends that a single scan can't, such as a connection slowly getting hotter.
Any repair work is carried out by our licensed electricians and certified where the regulations require it.
Frequently asked questions
What are the limitations of thermal imaging?
A thermal camera only sees surface temperatures in its line of sight, so it can't see inside cable runs, behind panels that stay closed, or through walls. Equipment must be under load, or faults stay cool and hidden. Shiny metal surfaces can reflect heat and mislead an untrained eye. Thermography complements electrical testing and inspection; it doesn't replace them.
Does the power need to be turned off for a thermal scan?
No, the opposite. Equipment has to be running under its normal load for problems to show up, so scans are done with the site operating. Covers on boards need to come off for the camera to see the connections, which is done under controlled conditions. Any repairs that follow may need a short, planned isolation.
Can you fix faults from a thermal report done by someone else?
Yes. If you already have a thermal imaging report from another provider, send it to us and our electricians can quote for the repairs it recommends. Having the original images helps us find each hot spot quickly and prioritise the work.
Is thermal imaging the same as test and tag?
No. Test and tag checks portable electrical equipment, such as leads and appliances, for safety. Thermal imaging looks at the fixed installation, mainly switchboards, connections and machinery, while it is working under load. They answer different questions, and many businesses use both as part of their regular maintenance.