Commercial & industrial electrical services, New ZealandOffice Mon–Fri 7.30am–5.00pm · 24/7 call-outs · info@phasesafe.co.nz

Inspections and testing

Switchboard surveys

A board-by-board survey of your site, with a report that shows what is fine, what needs fixing and what to plan for.

A switchboard survey records the condition, capacity, protection and labelling of every main switchboard, distribution board and sub-board on a site, and turns it into a plan. Phase Safe Electrical surveys switchboards for commercial and industrial buildings across New Zealand, from bases in Wellington and Auckland. The report rates each board, ranks what needs fixing, and shows which boards to budget for replacing, so you can plan the work instead of reacting to failures.

What is a switchboard survey?

A switchboard survey is an inspection of the switchboards on a site, done board by board, that records what each board is, what it feeds, what condition it is in and how much spare capacity it has. It differs from a general electrical inspection in its focus: the boards themselves, in enough detail to plan repairs, upgrades and replacements across a building or a whole property portfolio.

Most commercial buildings have more boards than people realise, many altered over the years by different contractors. The survey gives you one accurate list of every board and what it serves.

What does a switchboard survey check?

A switchboard survey checks each board's physical condition, protection, capacity, labelling and safety, along with anything that affects how it can be worked on. The table shows the main areas we look at and why each matters. The depth of testing is agreed with you before the survey, because some checks need power off.

Area What we look at Why it matters
Condition Enclosure, doors, covers, busbars, terminals, signs of heat, arcing or moisture Shows deterioration before it causes a fault
Protection Circuit breakers, fuses and RCD protection; ratings suited to the circuits Old rewireable fuses and missing RCDs are common defects
Capacity Spare ways, load on the board, room for new circuits Decides whether new equipment can be added
Labelling Every circuit and switch identified; schedules on the board Lets staff and electricians isolate the right circuit quickly
Safety Exposed live parts, barriers, earthing and neutral connections Identifies anything electrically unsafe now
Access and materials Clear access, mounting, and possible asbestos-containing backing boards Affects how the board can be repaired or replaced

These line up with the switchboard items insurers list in their periodic verification guidance, such as correct labelling and correctly rated protective devices.

When is a switchboard survey worth doing?

A switchboard survey is worth doing whenever you need to plan or justify spending on electrical infrastructure. Common triggers are buying or taking over management of a building, preparing a long-term maintenance plan, an insurer's request for evidence of switchboard condition, adding major load such as EV chargers or new plant, and boards that keep tripping or show signs of heat.

If one board is already showing problems, our guide on whether your switchboard needs upgrading covers the common signs.

What is in the switchboard survey report?

The report has one entry per board: its location, what it feeds, a condition rating, defects found, spare capacity and a recommendation to keep, repair, upgrade or replace. Recommendations are ranked by urgency, so the immediate safety items stand apart from the work that can be planned over the next few years. It ends with an overall summary for the site.

  • Board schedule. Every board, its location and what it supplies.
  • Priority list. Defects ranked from immediate to plan to monitor.
  • Capital planning. Which boards are near the end of their life, so replacements can be budgeted.

Because every item is described board by board, the report also works as a scope for comparing quotes.

Thermal imaging with a switchboard survey

Thermal imaging adds what a visual survey cannot see: a loose connection, an overloaded circuit or a failing breaker running hotter than the parts around it. The scan is done with the boards live and under normal load, and the results are added to each board's entry in the survey report, so hot spots and visible defects are ranked together in one list.

One insurer's risk guide recommends thermographic checks at least once a year, under load. Our thermal imaging service covers how a scan works.

Older boards and asbestos

Many older switchboards in New Zealand are mounted on backing boards that may contain asbestos. The survey flags boards that could, so that testing can be arranged before anyone drills, cuts or removes them. WorkSafe guidance sets out safe work methods for switchboards containing asbestos, and removing friable asbestos parts needs a Class A licensed asbestos removalist.

Share your building's asbestos survey or management plan with us beforehand, so the report can state which boards need special handling.

What happens after the survey?

After the survey you decide which items to act on and when. Immediate safety defects should be fixed straight away: the Electricity (Safety) Regulations 2010 say an owner must not use, or let others use, an installation that is electrically unsafe. Planned items can be grouped into a programme, so shutdowns are kept to a minimum and work on several boards is done together.

When a board needs replacing rather than repairing, our switchboard upgrades and distribution boards page explains how a replacement runs.

Frequently asked questions

How is a switchboard survey different from an electrical inspection?

A switchboard survey focuses on the switchboards: condition, protection, capacity and labelling, board by board, with a plan for each. A general electrical inspection covers the wider installation as well, including wiring, fittings and earthing throughout the building. Many sites use the survey for capital planning and the inspection for overall safety, and the two can be done in the same visit.

Does the power need to be turned off for a switchboard survey?

Not for most of it. The visual survey and thermal imaging are done with the boards live, and covers are removed under controlled conditions. Some tests, such as insulation resistance, need circuits isolated, so if they are included we plan short, staged shutdowns with you in advance. The scope agreed before the survey states which tests are included.

Can a switchboard survey help with insurance?

Yes. Insurers often ask commercial property owners for evidence that the electrical installation is checked and maintained, and their risk guidance names switchboard items such as labelling, protective devices and connections. A survey report, especially with a thermal scan, is evidence of that. Our insurance compliance page explains how we handle insurer requests.

Sources