Hazardous areas guide

Hazardous area classification and zones explained

Gas and dust zones, who classifies a site, and why the zone decides which electrical equipment can be used there.

Updated 16 November 2026

Hazardous area classification divides a site into zones according to how often, and for how long, an explosive atmosphere of gas, vapour or dust is likely to be present. Gas areas are Zone 0, 1 or 2; dust areas are Zone 20, 21 or 22. The zone decides which electrical equipment may be installed there. This guide helps you read classification drawings and reports from our hazardous area electrical inspections; it is not a method for classifying a site.

What is hazardous area classification?

Hazardous area classification is the assessment that identifies where an explosive atmosphere could form on a site, how likely it is, and how far it could extend. The result is a set of drawings and schedules that mark each zone around tanks, pumps, vents, filling points, booths and dust-handling plant. Everyone who works on equipment in those areas works from it.

An explosive atmosphere forms when a flammable gas, vapour, mist or dust mixes with air in the right proportions. For gases, that range sits between the lower and upper explosive limits. Classification looks at every source of release, such as a vent, seal or open container, and at ventilation, to decide each zone and its extent.

Gas zones: Zone 0, Zone 1 and Zone 2

Gas and vapour hazardous areas are divided into three zones by how often and how long an explosive gas atmosphere is present. Zone 0 is the highest risk, where it is present continuously, for long periods or frequently. Zone 1 is where it is likely occasionally in normal operation. Zone 2 is where it is not likely in normal operation and, if it does occur, lasts only a short time.

Zone When an explosive gas atmosphere is present Typical example
Zone 0 Continuously, for long periods or frequently Inside a vented petrol tank
Zone 1 Likely to occur occasionally in normal operation Close to a tank vent or filling point
Zone 2 Not likely in normal operation, and brief if it does occur Further out from a tank, inside the bund

WorkSafe guidance quotes the AS/NZS 60079.10.1 example of a vented petrol tank: Zone 0 inside the tank, Zone 1 around the shell and within 3 m of the vent outlet, and Zone 2 beyond that. Real distances depend on the substance, equipment and ventilation, so each site is assessed on its own.

Dust zones: Zone 20, Zone 21 and Zone 22

Combustible dust areas use three zones that mirror the gas zones. Zone 20 is where a cloud of combustible dust in air is present continuously, for long periods or frequently. Zone 21 is where a dust cloud is likely to occur occasionally in normal operation. Zone 22 is where it is not likely in normal operation and, if it does occur, persists only briefly.

Zone When an explosive dust cloud is present Typical example
Zone 20 Continuously, for long periods or frequently Inside a silo, hopper or dust collector
Zone 21 Likely to occur occasionally in normal operation Around bag-filling or tipping points
Zone 22 Not likely in normal operation, and brief if it does occur Areas where dust may escape from plant

Dust behaves differently from gas because it settles. A dust layer can insulate equipment so it runs hotter, and a small disturbance can lift it into a cloud. That is why dust classification also considers layers, and why housekeeping matters.

Which standards are used to classify hazardous areas?

In New Zealand, gas and vapour areas are classified to AS/NZS 60079.10.1:2022, and combustible dust areas to AS/NZS 60079.10.2. The Health and Safety at Work (Hazardous Substances) Regulations 2017 require a business using certain flammable gases, aerosols and liquids to establish a hazardous area that complies with the 2022 edition, or with a safe work instrument that covers hazardous areas.

The 2022 edition replaced the 2009 edition in regulation 10.6 from 30 July 2026, so older drawings may refer to the earlier standard. If yours predate the change, ask whoever prepared them whether a review is needed. The current dust standard is AS/NZS 60079.10.2:2016.

Who classifies a hazardous area in New Zealand?

The business that manages or controls work with the flammable substance is responsible for making sure the hazardous area is established. In practice the classification is prepared by people who understand the process, the substances and the plant, often a process or hazardous area engineer, working with site staff who know how the equipment is actually operated and maintained.

Classification should be reviewed whenever something changes: a new substance, a larger tank, different ventilation or relocated plant. The electrical inspector checks that installed equipment suits the classification and reports where the site no longer matches the drawings. If you have no classification drawings, that is the first gap to close.

Equipment protection levels and the zone

An equipment protection level (EPL) states how much protection a piece of equipment gives against becoming an ignition source. Gas equipment is rated Ga, Gb or Gc, and dust equipment Da, Db or Dc, with "a" the highest. Each zone sets the minimum level allowed. Equipment rated for a more hazardous zone can be used in a less hazardous one, but never the other way round.

Zone Equipment protection level allowed
Zone 0 Ga
Zone 1 Ga or Gb
Zone 2 Ga, Gb or Gc
Zone 20 Da
Zone 21 Da or Db
Zone 22 Da, Db or Dc

Equipment reaches its protection level through a protection concept shown in its Ex marking, such as flameproof (Ex d), increased safety (Ex e), intrinsic safety (Ex i), pressurisation (Ex p) or encapsulation (Ex m).

How the zone drives equipment selection

The zone sets the minimum protection level, but two more ratings must also match the substance: the group and the temperature class. Electrical equipment in a hazardous area has to suit all three. WorkSafe's guidance puts it simply: electrical equipment in a hazardous area must be suitable for the zone, or be placed at a safe distance outside it.

Gas and dust groups. Gases are grouped by how easily they ignite: IIA (propane), IIB (ethylene) and IIC (hydrogen, the most easily ignited). Dusts are grouped IIIA (combustible flyings), IIIB (non-conductive dust) and IIIC (conductive dust).

Temperature class. Equipment surfaces must stay below the temperature at which the gas or vapour would ignite on its own.

Temperature class Maximum surface temperature
T1 450°C
T2 300°C
T3 200°C
T4 135°C
T5 100°C
T6 85°C

A T4 item, for example, suits substances with an auto-ignition temperature above 135°C. The classes assume an ambient temperature of 40°C unless the marking states otherwise.

What classification means for electrical work on site

Because the classification decides equipment selection, every electrical change inside a zone needs checking against it. In New Zealand, installing or altering an installation in a hazardous area is high-risk prescribed electrical work under the Electricity (Safety) Regulations 2010. It must comply with AS/NZS 60079.14, be inspected, and be certified with a Certificate of Compliance and record of inspection.

That includes routine-looking jobs such as swapping a light fitting or adding a socket, and portable equipment carried into a zone can be an ignition source too. Tell any electrical contractor about your hazardous areas before they quote. Outside the zones, the site is covered by our commercial electrical inspections.

Frequently asked questions

What is the difference between Zone 1 and Zone 2?

It is how likely an explosive gas atmosphere is. In Zone 1 it is likely to occur occasionally during normal operation, for example near a vent or filling point. In Zone 2 it is not likely in normal operation and, if it does occur, lasts only a short time, such as from a leak. Zone 1 needs equipment rated Ga or Gb; Zone 2 accepts Ga, Gb or Gc.

Is hazardous area classification a legal requirement in New Zealand?

For many flammable substances, yes. Regulation 10.6 of the Health and Safety at Work (Hazardous Substances) Regulations 2017 requires a business using certain flammable gases, aerosols and liquids to establish a hazardous area that complies with AS/NZS 60079.10.1:2022 or a relevant safe work instrument. Combustible dust areas are classified using AS/NZS 60079.10.2, and the general duties of the Health and Safety at Work Act 2015 still apply.

What does T4 mean on electrical equipment?

T4 is a temperature class. It means the equipment's maximum surface temperature will not exceed 135°C, so it can be used where the gas or vapour present has an auto-ignition temperature above 135°C. The classes run from T1 at 450°C to T6 at 85°C. Equipment with a higher class number runs cooler and suits a wider range of substances.

Does New Zealand use the Class and Division system?

No. New Zealand classifies hazardous areas with the zone system in the AS/NZS 60079 series. Class and Division is the North American system, which you may see on imported equipment or overseas drawings. Equipment marked only for Class and Division needs checking before it is used in a New Zealand zone, because the markings do not translate directly.

Sources