Updated 16 November 2026
Test and tag is not a legal requirement in New Zealand. The legal requirement is that electrical equipment at work is safe and kept safe, and testing and tagging to AS/NZS 3760 is the recognised way to show it. This guide covers what the regulations say, how often equipment should be tested, what tag colours mean, who can do the testing and what records to keep. To book testing, see our test and tag service for workplaces.
Is test and tag a legal requirement in NZ?
No. WorkSafe and the Electrical Workers Registration Board (EWRB) both say testing and tagging is not mandatory. What is legally required is that equipment is electrically safe and maintained in a safe condition. Testing and tagging to AS/NZS 3760 is one recognised way to meet that, and it is the one the regulations name, so most workplaces use it.
WorkSafe leaves the decision to the business. If you choose not to test and tag, you still need another way to show plug-in equipment is safe, such as RCD protection and documented checks.
What do the Electricity (Safety) Regulations 2010 say?
Two regulations matter most. Regulation 15 says a person who owns or operates fittings or appliances must not use them, or let anyone else use them, if they are electrically unsafe. Regulation 26 says equipment used by an employee or contractor of its owner is deemed electrically safe if it has a current tag issued in accordance with AS/NZS 3760.
"Deemed to be electrically safe" is the key phrase. A current AS/NZS 3760 tag does not prove an item is safe forever, but it gives you a recognised basis for saying it was safe when tested. Schedule 2 of the regulations lists the edition: AS/NZS 3760:2022, In-service safety inspection and testing of electrical equipment and RCDs.
Regulation 26 also covers equipment you hire or lease out, and equipment supplied with premises you rent to someone else. For those, the equipment is deemed safe either with a current AS/NZS 3760 tag or if, when first made available, it is supplied through an RCD that protects against electric shock. Construction sites are covered separately under regulation 25, which points to AS/NZS 3012.
What does the Health and Safety at Work Act 2015 require?
Under section 36 of the Health and Safety at Work Act 2015, a PCBU (a person conducting a business or undertaking) must ensure, so far as is reasonably practicable, the health and safety of workers and others affected by the work. That includes providing and maintaining safe plant and a work environment without risks to health and safety. Plug-in electrical equipment falls under that duty.
The Act does not mention test and tag. It sets the outcome; testing to AS/NZS 3760, keeping records and withdrawing damaged equipment are common ways to show you have met it.
How often do you need to test and tag electrical equipment in NZ?
How often depends on the equipment and the environment it works in. WorkSafe gives the example that equipment used outside and in damp conditions on a construction site needs more frequent testing than a computer in an office. AS/NZS 3760 sets indicative intervals by environment, ranging from three months for hire equipment to five years for equipment that is never moved or flexed.
The table below is the indicative interval table from the 2010 edition of AS/NZS 3760, as reproduced with permission in Massey University's electrical safety procedure. The 2022 edition was a complete revision, so check the current standard before relying on a specific figure.
| Environment (AS/NZS 3760:2010) | Equipment test and tag | Portable RCD push-button test (by user) | Portable RCD operating-time test |
|---|---|---|---|
| Factories, workshops, places of work or repair, manufacturing, assembly, maintenance or fabrication | 6 months | Daily, or before every use | 12 months |
| Equipment or its cord flexed in normal use, open to abuse, or in a hostile environment | 12 months | 3 months | 12 months |
| Equipment and cord not flexed, not open to abuse, not in a hostile environment | 5 years | 3 months | 2 years |
| Accommodation areas of hotels, motels, hostels and similar | 2 years | 6 months | 2 years |
| Equipment used for commercial cleaning | 6 months | Daily, or before every use | 12 months |
| Hire equipment | Inspect before each hire; test and tag every 3 months | Before each hire | 3 months |
| Repaired, serviced or reintroduced equipment | After repair or service, or before return to service | – | – |
The row is set by where each item actually works, not by the type of business. A computer on a desk in a factory office follows the low-risk row, while the extension lead and heater in the same office follow the "flexed in normal use" row.
What are the rules for construction sites?
Construction and demolition sites follow AS/NZS 3012, which regulation 25 names for construction sites. WorkSafe's guide for small construction sites says RCDs should be tested with their test button every day, portable outlet assemblies should be tested by an electrician at least every three months, and a builder's temporary supply board needs a periodic assessment at least every six months.
For that assessment, a qualified electrical worker checks the board and issues a Certificate of Verification confirming it complies with AS/NZS 3000 and AS/NZS 3012. WorkSafe also says hire companies are responsible for testing and tagging hire equipment before you hire it.
Do test and tag colours mean anything in NZ?
Not legally. The Electricity (Safety) Regulations and WorkSafe's test and tag guidance do not set a colour scheme for tags. Colour schemes you see online, many of them from Australian sources, are not New Zealand law. Some New Zealand organisations use colours by choice: Massey University's procedure, for example, assigns a colour to each test year so out-of-date tags stand out.
What matters on any tag is the information. Tags typically show who tested the item, the test date, the retest date and a reference to AS/NZS 3760. If your site or head contractor uses a colour scheme, follow it, but always read the date.
Who can test and tag in NZ?
A competent person, who does not need to be an electrician. WorkSafe and the EWRB both say whoever does the testing must have the knowledge and skills to do it correctly and understand the standards involved, but does not need to be a registered electrical worker. A business can train its own worker or hire a third party, and must make sure that provider has the necessary training.
When Phase Safe does the testing, it is carried out by certified testers.
The line is drawn at repairs. Only a registered electrical worker can fix the problems testing reveals. After work that may affect an appliance's safety, regulation 90 says the person must test it to AS/NZS 5762 before releasing it, or disable and mark it if it is unsafe.
What records should you keep for test and tag?
Keep a register of every item and the results of each round of testing. WorkSafe recommends documenting results whenever electrical equipment is tested or inspected, and on construction sites, keeping the results on site. New Zealand regulations do not prescribe a format, so a clear register and report from each visit is the practical standard.
A useful test and tag register includes:
- A unique identifier for each item and a short description
- Where the item is kept or used
- The test date, the result and who did the test
- The next test date
- What happened to failed items: repaired, replaced or disposed of
Frequently asked questions
Is test and tag a legal requirement in NZ?
No. WorkSafe and the EWRB say testing and tagging is not mandatory. The legal duty is to keep electrical equipment safe, under the Electricity (Safety) Regulations 2010 and the Health and Safety at Work Act 2015. Equipment with a current tag issued under AS/NZS 3760 is deemed electrically safe under regulation 26, which is why most workplaces choose to test and tag.
How often do you need to test and tag electrical equipment in NZ?
It depends on the environment. The indicative table in AS/NZS 3760 (2010 edition) suggests every 6 months for factories and workshops, every 12 months for equipment that is flexed or in harsh conditions, and up to 5 years for equipment that never moves. Hire equipment is every 3 months. Construction sites follow AS/NZS 3012 and WorkSafe's construction guidance.
Who can test and tag in NZ?
Anyone competent to do it. WorkSafe says the tester must have the knowledge and skills to do the job correctly and understand the standards involved, but does not need to be a registered electrical worker. A business can train a worker or hire a provider. Repairing any fault the testing finds is different: only a registered electrical worker can do that.
Are test and tag colours compulsory in NZ?
No. New Zealand's electrical safety regulations and WorkSafe's guidance do not set a tag colour system. Colour schemes promoted online, many of them Australian, are not New Zealand law. Some New Zealand workplaces and head contractors use colours by choice so expired tags are easy to spot. Whatever the colour, the test date and retest date written on the tag are what count.
Is AS/NZS 3760 an Australian standard?
It is a joint Australian and New Zealand standard, prepared by a joint Standards Australia and Standards New Zealand committee. The current edition, AS/NZS 3760:2022, replaced the 2010 edition in June 2023. New Zealand's regulations reference it directly, but the legal framework around it differs between the two countries, so Australian testing rules do not automatically apply here.
Sources
- WorkSafe: Testing and tagging electrical appliances
- WorkSafe: Ensuring safety of plug-in electrical appliances
- WorkSafe: Electrical safety on small construction sites
- EWRB: Testing and tagging electrical appliances
- Electricity (Safety) Regulations 2010
- Electricity (Safety) Regulations 2010, regulation 26
- Health and Safety at Work Act 2015, section 36
- Standards New Zealand: AS/NZS 3760:2022
- Standards New Zealand: Corded and electric? Test it and tag it with AS/NZS 3760
- Massey University: Electrical Safety Procedure (AS/NZS 3760:2010 interval table)
- University of Auckland: Electrical equipment inspection