BWOF guide

Emergency lighting testing requirements in New Zealand

The routine checks, the yearly tests and the records that keep emergency lighting on your BWOF.

Updated 16 November 2026

In New Zealand, emergency lighting is tested at the frequency your building's compliance schedule sets. Where the schedule names AS/NZS 2293.2:2019, the routine service standard, testing follows its six-monthly and yearly service schedules plus longer-term checks. Emergency lighting is specified system SS4, so the testing feeds the building warrant of fitness. For the inspections themselves, see our BWOF and IQP inspections service.

How often does emergency lighting need testing?

Emergency lighting must be tested as often as the compliance schedule for your building says. Where the schedule cites AS/NZS 2293.2:2019, Standards New Zealand's published contents show its routine service schedules are set at six-monthly and yearly intervals, with further requirements every 10 years and at the end of an LED light source's life, plus a yearly condition report.

Read your own compliance schedule before relying on any general answer: older schedules may cite earlier documents, and each schedule can state its own procedures under section 103 of the Building Act 2004. A missed six-monthly service is a missed procedure. The BWOF states that the procedures were fully complied with for the previous 12 months, so a gap shows up at the anniversary date.

What the Building Code requires of emergency lighting

Building Code clause F6, visibility in escape routes, sets the performance emergency lighting must deliver. Its objective is to help safeguard people from injury in escape routes when the main lighting fails. Specified features, such as stairs, ramps, changes of direction, escape doors and obstructions, must stay reasonably visible, which the Code defines as visible from 10 metres or the greatest possible distance if less.

F6 also sets how fast the lighting must come on and how long it must run:

Location or building Requirement after main lighting fails
High-risk locations, such as areas with dangerous machinery or hazardous processes, or escape routes for more than 250 people 80% of design level within 0.5 seconds
Stairs and locations unfamiliar to users 10% within 0.5 seconds and 80% within 30 seconds
All other locations 10% within 20 seconds and 80% within 60 seconds
Risk group A: occupants must stay until lighting is restored, or evacuation takes longer than 90 minutes Operate until the main lighting is restored
Risk group B: evacuation takes 30 to 90 minutes, or occupant load is over 1,000 Operate for 90 minutes
Risk group C: all other buildings Operate for 30 minutes

What AS/NZS 2293.2:2019 covers

AS/NZS 2293.2:2019 is the joint Australian and New Zealand standard for routine service and maintenance of emergency lighting and exit signs. Standards New Zealand lists it as current, published on 9 April 2019, replacing the 1995 edition. It sets the criteria for keeping these systems working to their approved design until the next scheduled service, and sits alongside Part 1 on design and installation and Part 3 on the luminaires and signs themselves.

Its published table of contents covers:

  • Service intervals. The frequency and tolerances of routine service, with six-monthly, yearly, 10-yearly and end-of-light-source-life requirements set out in an appendix.
  • Baseline data. A record of the installation as designed, so later tests can be compared against it.
  • Procedures by system type. Separate procedures for self-contained fittings, central battery systems and LED luminaires and exit signs, including battery replacement.
  • Records and reporting. The format and content of service records, how long they are kept, how critical defects are handled, and a yearly condition report.

Your IQP should test to the edition your compliance schedule names.

What emergency lighting tests involve

Routine emergency lighting service combines a visual inspection of each fitting and sign with a test on battery power. The normal supply to the emergency circuits is interrupted so each fitting runs from its battery or the central battery, and the tester checks that it switches on and stays lit. Failures, damage and missing fittings are recorded and repaired, then retested.

The tests that run fittings on battery for a longer period are the ones that need the most planning, because the batteries then need time to recharge before the system is back to full capacity. How long each test runs and exactly what is checked at each interval come from the standard's six-monthly and yearly requirements and from your compliance schedule. We test to whichever one your schedule cites.

Self-contained and central battery systems

There are two main ways an emergency lighting system is powered. In a self-contained system, each luminaire or exit sign has its own battery and charger. In a central battery system, a single battery bank in a plant room feeds the emergency fittings through dedicated circuits. AS/NZS 2293.2:2019 has separate service procedures for each, and for LED luminaires and exit signs.

Central battery systems put more weight on the battery bank, charger and distribution circuits. Either way, the compliance schedule should describe the type of system installed, since section 103 requires each specified system's type, and its make if known, to be stated.

Exit signs and evacuation signs

Exit signs and other signs that help people evacuate are inspected with the emergency lighting, because AS/NZS 2293.2 covers both emergency lighting and exit signs. On the compliance schedule, signs appear under SS14, which covers emergency power systems and signs relating to systems SS1 to SS13, or under SS15(d), signs that form part of a building's means of escape from fire.

Illuminated exit signs have batteries and light sources like emergency luminaires, and are serviced under the same standard. Building Code clause F6 also requires signs to indicate escape routes as set out in clause F8, so a missing, dark or damaged sign is a defect to fix promptly, not something to leave for the next service.

Records your BWOF needs

Every emergency lighting test needs a record: the date, who did the work, which fittings and signs were tested, the results, and what was repaired. Section 110 of the Building Act 2004 requires the owner to obtain annual written reports signed by each person who carried out procedures, and to keep them with the compliance schedule for two years for the council to inspect.

Wellington City Council lists the records to keep as inspections and tests, preventative maintenance, faults found and repair work, and Auckland Council lists emergency lighting among the safety systems its audits look at. At the anniversary, the IQP's Form 12A for SS4 goes with the BWOF. Our guide to compliance schedules and specified systems explains where SS4 and SS14 fit on the schedule.

Who can test emergency lighting?

Emergency lighting for a BWOF is inspected and certified by an independently qualified person (IQP) accepted by the council for SS4. Section 103 of the Building Act 2004 allows a compliance schedule to give some procedures to other persons, so check yours for any routine checks assigned to the owner or building manager. Repairs to the fixed wiring are electrical work for a licensed electrician.

Councils set the criteria for SS4 registration. Wellington City Council, for example, looks for knowledge of AS 2293.1, AS/NZS 2293.1 and NZS 6742 and the Building Code clause F6 requirements, plus at least four years of relevant current industry experience. Our guide to what an IQP is explains how registration works and how to check an IQP.

Planning tests around a working building

Battery tests leave the emergency lighting at reduced capacity until it recharges, so they need planning in an occupied building. Practical options are to test outside the busiest hours, to test in sections so part of the building always has full cover, and to avoid testing just before a period when the building will be busy.

Timing is agreed with you before each service. Emergency lighting can sit within planned and predictive maintenance visits, and failures found between services are handled through our fault finding and 24/7 call-outs.

Frequently asked questions

How long must emergency lighting last in New Zealand?

Building Code clause F6 sets the duration by risk group. Buildings in risk group C, meaning any building not in groups A or B, need 30 minutes. Risk group B, where evacuation takes 30 to 90 minutes or more than 1,000 people occupy the building, needs 90 minutes. In risk group A, where occupants must stay or evacuation takes longer than 90 minutes, the lighting must run until the main lighting is restored.

What qualifications do you need to test emergency lighting?

For a BWOF, emergency lighting is certified by an IQP that the council has accepted for SS4. Councils set their own criteria. Wellington City Council's, for example, cover knowledge of the emergency lighting standards and Building Code clause F6, plus at least four years of relevant industry experience. Repairs to the fixed wiring must be done by a licensed electrical worker under the Electricity Act 1992.

Do LED emergency lights still need testing?

Yes. LED emergency luminaires and exit signs are still part of the specified system, and the batteries that power them still age and lose capacity. AS/NZS 2293.2:2019 has specific procedures for LED luminaires and exit signs, including requirements at the end of the light source's life, as well as the six-monthly and yearly service that applies to all fittings.

What happens if an emergency light fails its test?

The failure is recorded, and the fitting, battery or circuit is repaired and retested. AS/NZS 2293.2:2019 includes requirements for handling critical defects, and the repair forms part of the records the owner keeps. A failed fitting left unrepaired means the system is not performing to its standard, which the owner must ensure under section 105 of the Building Act 2004.